Protection relay tester’s basic knowlage – Description of impedance charactroistic
In power system protection, the impedance characteristic refers to the ability of a relay to detect faults based on the impedance (or admittance) presented to it.Impedance opposes the flow of electrical current in a circuit, consisting of resistance and reactance. The characteristic of impedance is crucial for the operation of distance relays. These relays are designed to activate when they measure impedance between their location and the point of fault that surpasses a certain threshold.
Distance relays use impedance characteristics to determine the location of a fault on a transmission line or within a substation. They do this by comparing the measured impedance to a set of pre-defined boundaries or zones. These zones are typically represented on an R-X (resistance-reactance) diagram, which is a graphical representation of impedance
Relay protection tester is basic testing tool to search boundary of impedance.
The significance of impedance characteristic boundary search in relay protection includes:
Fault Detection and Localization: By defining the impedance boundaries, relays can accurately detect and locate faults within their zone of protection, which helps in quickly isolating the faulted section and minimizing the impact on the rest of the power system.
Selectivity: Impedance boundary search allows for selective tripping of circuit breakers. This implies that only the relay nearest to the fault will trigger, leaving the relays at greater distances inactive. This ensures that the system isolated the fault without disconnecting unnecessary, healthy sections of the system.
Relay Coordination: Proper setting of impedance boundaries is essential for coordinating the operation of multiple relays in a power system. This coordination ensures that the relays respond to faults in a predetermined order, preventing maloperation and cascading failures.
System Stability and Reliability: Maintaining accurate impedance characteristics is essential for system stability, as it ensures engineers cleard faults promptly and efficiently. This reduces the risk of system collapse.
In summary, the impedance characteristic boundary search is a critical function of distance relays, ensuring to detect and isolate system faults promptly, and that the power system remains stable and reliable
Impedance boundary searching is the basic function of a professional relay protection tester
Types of Boundary of Impedance in
Polygon Impedance Boundary
operation of relay protection tester:
Select Polygon Characteristic: Choose the polygon characteristic from the options provided.
Data Input Mode: Select either ‘R-X’ (Resistance-Reactance) or ‘Z-Φ’ (Impedance-Phase) mode.
Set Coordinates: Begin by setting the first point of the polygon, typically at the origin (0,0), which represents the point of the relay location.
Add Points: Continue to add subsequent points to define the polygon’s vertices. These points are set in the ‘angle point’ column.
Construct the Line: Each pair of points will form a line segment of the polygon.
Set Parameters: You can set resistance (R) and reactance (X) to negative numbers if needed.
Draw the Curve: Click the ‘drawing’ button to generate the theoretical impedance boundary curve and the error curve.
Drawing a Circle Impedance Boundary with relay tester
operation of relay protection tester:
Select Circle Characteristic: Choose ‘Circle’ from the characteristic options.
Set Parameters: Input the ‘setting impedance’, ‘angle of impedance’, and ‘offset’ quantity.
Real-time Display: The interface will show the circle’s real-time figure as you set the parameters.
Set Scanning Radius: Click the center of the diagram to set the scanning radius and step size for the boundary search.
For ‘Z (V) Characteristic Curve’ testing, the process is similar to the ‘Z (I) characteristic curve’.
Characteristic Curve Testing
Select Test Item: Choose ‘Z (I) characteristic curve’ for testing the relationship between current and impedance.
Parameters Set: Set the origin point, length, and angle of the searching beam, as well as the original and final values of the current.
Observe the Diagram: The actual effect diagram will be displayed after setting these parameters.
Testing Process: The process is similar to that of a differential relay test. Impedance starts at 0 and increases in set steps, testing the operating current of protection at every impedance value.
Result: Once the test is complete, the software will automatically draw the corresponding curve.
VAE-430
Ecnomical 4U3I Relay Tester
$
21*0
set
-
4*120V -
3*40A -
OEM available
Order Now
Popular
VAE-660
Ecnomical 6U6I Relay Tester
$
51*9
Set
-
6*120V -
6*30A -
Free applications
Order Now
Popular
VAH430
High Accuracy 4U3I Relay Tester
$
81*9
Set
-
4*120V -
3*40A -
AC accuracy 0.1%
Order Now
Popular